← Back to Cedrix
Sample Report · 01 / 04
Splunk MCP Monitor · Cedrix v1.8.0
cedrix.io · info@cedrix.io
📝 Prompt
"Run the 'average gas consumption (Nm³/kWh)' search and analyze the results."

Summary statistics

0.3246
Highest
(GM16)
0.2720
Plant average
(GM07)
0.2188
Lowest
(GM31)
+48.5%
Variance
range

Per-motor gas consumption

GM16
0.3246
GM19
0.3236
GM02
0.3233
GM15
0.3228
GM20
0.3225
GM07 (avg)
0.2720
GM30
0.2602
GM23
0.2339
GM31 ✅
0.2188

🔴 Critical group — high consumption (> 0.32)

#MotorAverageMaxMinVarianceReadsStatus
1GM160.32460.54270.24610.2966638Low efficiency
2GM190.32360.54900.04140.5076 ⚠563Unstable
3GM020.32330.54990.05880.4911615Faulty
4GM150.32280.55970.00800.5517 ⚠1,035Highest variance
5GM200.32250.57070.04410.5266563Inconsistent

5 motors > 0.32 → 17–48 % above plant average.

© 2026 CEDRIX · Sample Report — anonymized 1 / 2
Sample Report · 01 / 04
Gas Consumption Analysis · Page 2
cedrix.io

🟢 Efficient group (< 0.27)

MotorAverageVarianceStatus
GM310.21880.3378⭐ Most efficient
GM230.23390.4226Efficient
GM250.23490.4854Efficient
GM220.23820.4852Efficient
GM280.25840.6072Good
GM300.26020.3619Good

🟡 Warning group (0.27–0.32)

MotorAverageVarianceReads
GM070.27200.33501,440
GM060.27170.32581,440
GM040.27110.32951,440
GM030.27100.33291,440
GM110.27090.33031,439
GM130.27040.32321,440
GM010.26960.36611,438
GM090.26940.37411,440

Critical findings

GM16, GM19, GM02 — abnormally high consumption. GM19 variance 0.0414–0.5490 → sensor fault indicator. GM02 NonDriveEnd bearing-temperature anomaly correlates; the reactive-power circuit should be inspected.
GM15 — extreme variance (min 0.008 / max 0.5597). Suspect control-system faults or sensor-calibration drift.
GM31 — reference motor. Stable at 0.2188 Nm³/kWh. Use as the best-practice benchmark for the rest of the fleet.

Recommended actions

PriorityMotorActionExpected gain
🔴 UrgentGM19Verify sensor calibration+5 – 10 % efficiency
🔴 UrgentGM02Inspect reactive-power circuit+8 – 12 % efficiency
🔴 UrgentGM16Review motor control system+10 – 15 % efficiency
🟡 ImportantGM15Sensor calibration (high variance)+5 – 8 % efficiency
🟢 InfoGM31Use as best-practice reference
🛡
Data sovereignty: Site name, customer code, location and operator identity were anonymized by the Cedrix masking engine before the AI request. IP addresses and organization details are redacted in this sample.
© 2026 CEDRIX · cedrix.io · info@cedrix.io · +90 532 331 24 18 2 / 2